United Parcel Service's Tier 4 data center goes green


Matt Stansberry, Senior Site Editor
01.21.2008
Rating: -4.17- (out of 5)


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


*Editor's note: This is a two-part case study. Part one focuses on how UPS identified wasted cooling, and in doing so cut out the CRAHs. Part two is about UPS's water-side economizer use and other power-saving cooling strategies.
Let's face it: A lot of green data center case studies are pretty worthless. Vendors and customers pat one another on the back for buying green products and offer vague promises to save energy in data centers over a period of time.

But the facilities department at the United Parcel Service of America Inc.'s Alpharetta, Ga., site are about to save you a lot of money on your data center air-conditioning bill today. Joe Parrino, data center manager at UPS' Windward data center also explains his organization's load-shedding process and proves that using outside air to cool a data center can work—even in the hot temperatures of the southeastern U.S.

Brown goes green in the data center
UPS' Windward data center bucks the conventional wisdom. Old data center facilities are supposed to be inefficient, and outdated mechanical systems are primarily to blame. Even worse, considering the amount of redundancy designed into the facility to prevent downtime, an Uptime Institute Tier 4-rated data center would have to be a real energy hog.

But somehow the 13-year-old, Tier 4 facility in Alpharetta scores a power use effectiveness (PUE) as low as 1.9 or, in the Uptime Institute's parlance, SI-EER. This ratio represents the measure of the power going into the facility at the utility meter divided by the power going to the IT load, measured either at the power distribution unit or uninterruptible power supply.

In the case of the Windward data center, PUE was measured at the output of the uninterruptible power supply; measuring the o...


BROWSE BY TAG
Data center power consumption and savings,   Data center design and infrastructure,   Data center power management,   Infrastructure Management Tips,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center power consumption and savings
Sizing computer room air conditioners for data center energy efficiency
IBM VMworld news in brief
Air-side and water-side economizers in the data center
How to choose the right uninterruptible power supply for your data center
Avoid common pitfalls when calculating data center power load
Amazon data center facility engineer touts radical cooling tactics
The TPC Energy Specification: Energy consumption vs. performance and costs
Measuring data center energy consumption in watts per logical image
Data center managers plan for power density jumps
Backup power in a shipping container: Active Power's PowerHouse

Infrastructure Management Tips
Grow a green business: Cut costs and improve energy efficiency with green IT
Closing the green gap: Expanding data centers with environmental benefits
Green data center site selection: Cost versus sustainability
Improving data center cooling capacity with chilled water plants
How to prepare for remote data center maintenance trips
DC Pro: a breakdown of a data center efficiency tool
Selecting a general contractor: Data center construction runbook, Chapter 3
Selecting a winning data center design team: Data center construction runbook, Chapter 2
Protecting your data center from real show-stoppers: Preparing a disaster recovery plan
Economizer performance: Applying CFD modeling to the data center's exterior

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
power usage effectiveness (PUE)  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary


utput of the PDU was too difficult. For a more detailed discussion of the differences in measuring at the power distribution unit versus at the uninterruptible power supply, listen to the podcast "Where to measure IT vs. infrastructure power use: PDU or UPS?" with Pitt Turner.

According to the Uptime Institute, the average ratio is 2.5. This means that for every 2.5 watts going "in" at the utility meter, only 1 watt is delivered out to the IT load. In this regard, United Parcel Service's Windward data center is way ahead of the curve. But how did the company do it?

Cutting out the air handling units
Forced-air cooling is one of the least efficient systems in data center infrastructure, and wasting cold air is the most common mistake in data center management. You can set up hot aisle/cold aisle, install blanking panels, and seal gaps in the floor, but you've probably still wasted cold air in a place you wouldn't expect: the perforated top of power distribution units.

Parrino's staff learned this by chance. The team noticed the perforated roof on a PDU as it sat in a hallway waiting for installation. They took airflow measurements on several installed units using a velometer and calculated the cubic-feet-per minute (CFM) loss (i.e., the velocity of the air multiplied by square footage of the opening). United Parcel Service determined the units lost 2,000 CFM per PDU.

"What heats up inside a PDU that would require 2,000 CFM of cooling?" Parrino wondered. The only component possibility was transformers, which have a high temperature tolerance. So Parrino conducted an experiment. He ran a PDU with a solid Lexan cover at full load (i.e., 180 kW) using a load bank for one hour in an outside location on an 85 degree Fahrenheit day. Measurements of the transformer temperatures were taken with an infrared camera. The transformer temperatures increased 20 degrees from the nominal 115 degrees on the conditioned raised-floor space to about 135 degrees in a non-air-conditioned location. This was well within the manufacturer's stated 300-plus degrees Fahrenheit operating range. "We didn't even come close to the shutdown temperature," Parrino said.

The next step was to seal the top of PDUs with Lexan covers. Parrino hired a contractor to install covers on all the units. The covers have a three-inch opening to ensure that the transformers get airflow but also block 90% of undesirable bypass airflow. Following the installation of the Lexan covers, average transformer temperature increase was around 1 degree to 2 degrees Fahrenheit.

"After we installed the covers, we looked at the under-floor static pressure and we were amazed at what we got back," Parrino said. The data center had 62 PDUs that were wasting 124,000 CFM of cold air. With the covers installed, Parrino estimated that he could shut off six computer room air handlers [CRAH] based on measured airflow of 19,000 CFM per CRAH unit. In reality, he shut off 10.

The cost of covering PDUs was about $6,000, and United Parcel Service estimated that payback would take about 4.3 months. Instead the project actually paid for itself in only a month and a half.

Parrino said he plans to implement variable frequency drives on some of Windward's CRAH units, and his team is experimenting with variable air volume floor grates controlled by intake temperatures of the racks. "This will slow the consumption of CRAH fan energy even further by delivering the CFM that's needed for each rack instead of delivering based on the worst-case IT load," Parrino said.

>>>go to part 2>>>

ABOUT THE AUTHOR: Matt Stansberry is SearchDataCenter.com's senior site editor. Write to him about your data center concerns at mstansberry@techtarget.com.

Rate this Tip
To rate tips, you must be a member of SearchDataCenter.com.
Register now to start rating these tips. Log in if you are already a member.




DISCLAIMER: Our Tips Exchange is a forum for you to share technical advice and expertise with your peers and to learn from other enterprise IT professionals. TechTarget provides the infrastructure to facilitate this sharing of information. However, we cannot guarantee the accuracy or validity of the material submitted. You agree that your use of the Ask The Expert services and your reliance on any questions, answers, information or other materials received through this Web site is at your own risk.



White Papers - Data Center Networking

The Intel IT Technology Center - Power, Performance and Mobility Solutions

HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts