How popular are grate-type tiles in a data center's raised floor design?


Robert McFarlane
04.27.2006
Rating: -4.20- (out of 5)


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


I don't see mentioned too often the use of grate-type perforated tiles such as Tate's GrateAire that offers a 58% open area as opposed to the typical 25% perforated tile open area in raised-floor data center designs.. Is the grate-type tile finding a place in computer rooms?

The grate-type tiles are a godsend -- but only if they're used correctly and the parameters are well understood. Unless you really know what your under-floor air flow is doing, installing grate-type tiles can deprive other parts of your floor of the air they should be getting. Remember, you can't get more air out of the floor than the CRAC has put in it. Since most data centers lose a significant percentage of their air in uncontrolled leaks and the under-floor air flow and pressures are uneven to begin with, it's highly unlikely that you have all the air your CRACs are delivering actually available at the tiles you install.

So you not only need to be concerned about how much air goes through which tiles, but you also need to be very knowledgeable about exactly where you install grate-type tiles. If you put them in a place where air volume and pressure are already low, they're going to do little for you and will probably make things worse somewhere else. Other then trial and error, the best way to make these determinations is through CFD modeling.

Also keep in mind that, while the GrateAire tile offers 58% open area, this is only if the tile does not have a damper. Dampered tiles allow you to control the air flow at each location so that you don't waste air in places where less cooling is needed. However, the dampered GrateAire tile has a maximum open area of only about 33%. This is not a whole lot better than a fully open standard perforated tile, so we don't specify it very much. But since the 58% open tiles affect under-floor air volume and pressure, we use them very carefully and only after performing a thorough CFD analysis.

Rate this Tip
To rate tips, you must be a member of SearchDataCenter.com.
Register now to start rating these tips. Log in if you are already a member.




BROWSE BY TAG
Data center design and infrastructure,   Data center power management,   Infrastructure Management Tips,   Data center design and infrastructure,   Raised floor cooling,   Chapter 3: Data center cooling,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center power management
Backup power in a shipping container: Active Power's PowerHouse
U.S. Bowling Congress moves data center, halves energy costs
Tom Friedman to data centers: 'Get ready for carbon tax'
Google opts for battery backup over UPS: News in brief
CRG West preps data centers for cloud computing customers
ViaWest data centers go green, which makes dollars and cents
Common data center hurdles: Cooling and power distribution problems
Data center power consumption: Key theme at DCD
Data center managers face mountains of technology shifts
Welsh data center expected to be Europe's most advanced
Data center power management Research

Infrastructure Management Tips
Grow a green business: Cut costs and improve energy efficiency with green IT
Closing the green gap: Expanding data centers with environmental benefits
Green data center site selection: Cost versus sustainability
Improving data center cooling capacity with chilled water plants
How to prepare for remote data center maintenance trips
DC Pro: a breakdown of a data center efficiency tool
Selecting a general contractor: Data center construction runbook, Chapter 3
Selecting a winning data center design team: Data center construction runbook, Chapter 2
Protecting your data center from real show-stoppers: Preparing a disaster recovery plan
Economizer performance: Applying CFD modeling to the data center's exterior

Raised floor cooling
Raised floor bests overhead cooling, IBM finds
Block those holes!
Raised floors and efficiency: Controlling cooling matters
Is your cabling ruining your efficiency?
Data center raised floors and ceiling height

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary

DISCLAIMER: Our Tips Exchange is a forum for you to share technical advice and expertise with your peers and to learn from other enterprise IT professionals. TechTarget provides the infrastructure to facilitate this sharing of information. However, we cannot guarantee the accuracy or validity of the material submitted. You agree that your use of the Ask The Expert services and your reliance on any questions, answers, information or other materials received through this Web site is at your own risk.



White Papers - Data Center Networking

The Intel IT Technology Center - Power, Performance and Mobility Solutions

HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts