What's the best way to install a wall vapor barrier?


Robert McFarlane
04.27.2006
Rating: -3.67- (out of 5)


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


We have a 5,000 square foot computer room in the interior of a 40,000 square foot office, which is one floor of multi-story building. The computer room wall is 2HR rated with noise batts.

Where should the vapor barrier be placed: on the interior side or the exterior side of the metal studs? What is the best type of barrier to use: poly sheeting, foil-faced insulation or foil-faced gypsum?

This is one of the best posed questions I have ever been asked. Unfortunately, the answer could be debated for years, just as the same question continues to be debated with regard to house construction, which one would think had been resolved years ago. There is even a question as to whether a vapor barrier is needed at all for an interior data center, but since most people call for it, I can at least tell you what we recommend and why, as well as give you a little of the "debate" thinking.

First of all, the purpose of a vapor barrier is to keep condensation out of insulation, since moisture reduces the insulating value, and to keep it from ultimately rotting the insides of walls. (If the walls don't go from floor to the slab above, this is not a concern since moisture can escape out of the open walls at the top, but a data center wall should be slab-to-slab, both to maintain the interior environment and to provide the fire rating.) The generally accepted rule is that the vapor barrier goes on the warmer side of the wall. The reasons are two-fold. First, warmer air migrates toward colder air, and one would hope that the offices would not normally reach the temperature of the data center; second, warm air is inherently capable of holding more moisture than cold air, so the normal assumption is that any condensation will take place on the warmer side of the wall as the more moist air migrates to the colder side. The goal, therefore, is to stop the moisture before it gets into the insulation.

Assuming you are in the North, in summer the building air conditionin...


BROWSE BY TAG
Data center design and infrastructure,   Data center power management,   Infrastructure Management Tips,   Data center design and infrastructure,   Chapter 3: Data center cooling,   Data center cooling metrics and design,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center power management
Backup power in a shipping container: Active Power's PowerHouse
U.S. Bowling Congress moves data center, halves energy costs
Tom Friedman to data centers: 'Get ready for carbon tax'
Google opts for battery backup over UPS: News in brief
CRG West preps data centers for cloud computing customers
ViaWest data centers go green, which makes dollars and cents
Common data center hurdles: Cooling and power distribution problems
Data center power consumption: Key theme at DCD
Data center managers face mountains of technology shifts
Welsh data center expected to be Europe's most advanced
Data center power management Research

Infrastructure Management Tips
Grow a green business: Cut costs and improve energy efficiency with green IT
Closing the green gap: Expanding data centers with environmental benefits
Green data center site selection: Cost versus sustainability
Improving data center cooling capacity with chilled water plants
How to prepare for remote data center maintenance trips
DC Pro: a breakdown of a data center efficiency tool
Selecting a general contractor: Data center construction runbook, Chapter 3
Selecting a winning data center design team: Data center construction runbook, Chapter 2
Protecting your data center from real show-stoppers: Preparing a disaster recovery plan
Economizer performance: Applying CFD modeling to the data center's exterior

Data center cooling metrics and design
Improved airflow cools off overheated data center
Fears of cooling with outside air may be unfounded
Using ASHRAE specs for data center metrics
How do I measure cooling consumption?
The total cost of cooling
Cooling data centers: A look toward the future
New cooling technologies could cut energy costs
Monitoring temperature in the data center
Cooler rooms or cooler servers?

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary


g will remove moisture so humidity will be relatively low. In winter, heating will increase air temperature, but the outside air will be crisp and very low in humidity. If you are in the South, you will have high heat and humidity outside in summer, which the air conditioning will reduce, but not as much as in the North. In winter you may still use air conditioning in regions where it never gets really cold, which means lower humidity as well. So to start with, no one analysis holds completely true for every part of the country, but we can still draw a general rule. For an interior data center such as you describe, the "office" or "exterior" side of the wall should still be "warmer" than the data center side.

However, this is where things get a little sticky. In a data center, we are not only cooling to levels below the normal office environment. We are also forcing the humidity to abnormal levels relative to the temperatures we are running. Therefore, it is a virtual certainty that the data center will be both colder and more humid than the offices, at least while building environmental systems (heating or air conditioning) are operating in the office areas. This is not in line with "norms." So even though we would usually think of warmer air as also being more humid, this doesn't hold true between offices and the data center, which throws a bit of a monkey wrench into conventional theory -- except for one thing: While we specify both a relatively low temperature and a relatively high humidity range for the data center, we always tack on the words "non-condensing." Obviously, we don't want a situation where moisture starts condensing on cabinets or equipment, so this phrase makes sure the air coming out of the CRAC units is not made so cold in order to cool the equipment that it is below the dew point when humidity is added. And if it won't condense on our equipment surfaces, it certainly won't condense on or in the interior wall. Therefore, the "outside" wall is still the place where any concern might arise. But let's recognize that this condition is likely to arise only on summer weekends or holidays when building systems are shut down and the office air truly becomes both hot and more humid than that in the data center.

As to the best type of vapor barrier to use, as can be seen from the above description, the barrier itself isn't really going to do much of anything most of the time, so this is not a major concern. Contractors love poly sheeting, but it is more easily damaged and compromised during construction than most any of the other materials. You mention that your insulation is for noise-control purposes, so foil-faced insulation is probably not a good choice (unless it's rigid board insulation) since standard batt insulations do not have the density to provide much sound attenuation. But thermal control inside the data center is usually the reason for insulating the wall, not sound attenuation, since it is expensive to maintain a good data center environment and thick, loose batts are the right choice for that purpose. If you also want noise control, it would probably be best to use thermal insulation between the studs, put a layer of rigid, noise control fiberglass under the gyp board on the data center side of the wall and use foil-faced gyp board on the office side. But frankly, for the amount of condensation control you are actually dealing with, the specific type of vapor barrier is not very important. Whatever your contractor is most comfortable installing is probably the best choice.

Rate this Tip
To rate tips, you must be a member of SearchDataCenter.com.
Register now to start rating these tips. Log in if you are already a member.




DISCLAIMER: Our Tips Exchange is a forum for you to share technical advice and expertise with your peers and to learn from other enterprise IT professionals. TechTarget provides the infrastructure to facilitate this sharing of information. However, we cannot guarantee the accuracy or validity of the material submitted. You agree that your use of the Ask The Expert services and your reliance on any questions, answers, information or other materials received through this Web site is at your own risk.



White Papers - Data Center Networking

The Intel IT Technology Center - Power, Performance and Mobility Solutions

HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts