Additional air conditioners still not cooling hot areas


Robert McFarlane
04.27.2006
Rating: -4.33- (out of 5)


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


We have installed additional air conditioners in our data center, but it hasn't made much of a difference in the hot areas. Our cabinets are installed face-to-face and back-to-back as we see recommended for hot aisle/cool aisle setups. What could be wrong?

There is a long list of possibilities, but let's assume that these are down-blow units delivering air under the raised floor, that the air conditioners are all set for the same temperature and humidity, that the sensor calibrations have been field-checked by the manufacturer, that they are running as they were designed, and that the equipment cabinets have either highly perforated doors, or no doors, so air can flow freely into the equipment.

The three primary causes of poor air delivery are bypass air, air leakage, and under-floor blockage.

Bypass air is simply air from the hot aisle getting back into the cold aisle and going back through the equipment, or vice-versa (cold air going through into the hot aisle). Every unused space in every cabinet should have a blank panel installed. In future use cabinets that have no equipment installed, at least tape a piece of heavy construction plastic inside to separate the front from the back. Also block any spaces between cabinets. And never install perforated tiles in the hot aisle. It not only wastes useful cold air; it also lowers the return air temperature, making the air conditioners think less cooling is...


BROWSE BY TAG
Data center design and infrastructure,   Data center power management,   Infrastructure Management Tips,   Data center design and infrastructure,   Chapter 3: Data center cooling,   Mitigating data center hotspots,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center power management
Backup power in a shipping container: Active Power's PowerHouse
U.S. Bowling Congress moves data center, halves energy costs
Tom Friedman to data centers: 'Get ready for carbon tax'
Google opts for battery backup over UPS: News in brief
CRG West preps data centers for cloud computing customers
ViaWest data centers go green, which makes dollars and cents
Common data center hurdles: Cooling and power distribution problems
Data center power consumption: Key theme at DCD
Data center managers face mountains of technology shifts
Welsh data center expected to be Europe's most advanced
Data center power management Research

Infrastructure Management Tips
Grow a green business: Cut costs and improve energy efficiency with green IT
Closing the green gap: Expanding data centers with environmental benefits
Green data center site selection: Cost versus sustainability
Improving data center cooling capacity with chilled water plants
How to prepare for remote data center maintenance trips
DC Pro: a breakdown of a data center efficiency tool
Selecting a general contractor: Data center construction runbook, Chapter 3
Selecting a winning data center design team: Data center construction runbook, Chapter 2
Protecting your data center from real show-stoppers: Preparing a disaster recovery plan
Economizer performance: Applying CFD modeling to the data center's exterior

Mitigating data center hotspots
Data center cooling strategies: Overheating server prevention
Liquid-cooled refrigerants solve density hot spots
Hot spots not so hot in the data center
Backup CRAC: Avoid a summer server meltdown

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary


needed, which also happens when cold air bypasses through cabinets into the hot aisle.

Air leakage comes through openings in the floor that do not deliver useful air to the equipment. Cable holes under racks and cabinets; gaps between the floor tiles and the walls or air conditioners, or around conduit penetrations; missing tiles; perforated tiles where there is no equipment; gaps between poorly aligned tiles; perimeter walls that do not extend to the floor or have openings to adjacent rooms – all these not only waste cold air, but also reduce the air pressure under the floor which lowers air delivery through the tiles that need it. Fill and seal gaps, get tiles re-aligned, install under-floor air dams to keep air within the data center, and install good quality seals (such as those from air distribution optimization product maker, KoldLok) on cable openings.

Under-floor blockage is usually due to large cable pile ups in front of air conditioners and/or under too low a raised floor. Floors of 12-in. height or less are destined to have problems, but higher floors can also be over-filled. Power and cable runs must be planned so as to avoid blocking air flow, and cables must be spread out in order to reduce air dam situations.

There are many more factors that affect data center cooling, but until the above are addressed, it is probably not worth the effort to delve into the more complex possibilities.


Rate this Tip
To rate tips, you must be a member of SearchDataCenter.com.
Register now to start rating these tips. Log in if you are already a member.




DISCLAIMER: Our Tips Exchange is a forum for you to share technical advice and expertise with your peers and to learn from other enterprise IT professionals. TechTarget provides the infrastructure to facilitate this sharing of information. However, we cannot guarantee the accuracy or validity of the material submitted. You agree that your use of the Ask The Expert services and your reliance on any questions, answers, information or other materials received through this Web site is at your own risk.



White Papers - Data Center Networking

The Intel IT Technology Center - Power, Performance and Mobility Solutions

HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts