Seven steps to data center fire planning


Lance D. Harry, Contributor
07.14.2005
Rating: -3.75- (out of 5)


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


A complete and thorough fire protection strategy in the data center seems like an obvious priority. However, often the decisions are left up to those without a vested interest in the assets and operation of the facility. Here are a number of points you may want to address before deciding which fire protection strategy is best for your data center.

1. Protection = detection + suppression. The ideal protection strategy should include a smoke detection package with a fire suppression system. There are a variety of possibilities to choose from in both categories.
  • Detection. Typically, detection is cross-zoned using both photoelectric and ionization type spot detectors. Cross zoning allows the end user protection against false discharges of the suppression system, by requiring one of each type of detector to be in alarm, prior to the initiation of a discharge. High sensitivity smoke detection is also an option. This air aspirating technology allows the earliest possible detection of a combustion event. However, HSSD should never be used to initiate the discharge of a suppression system.

  • Suppression. There are multiple options to choose from for both suppression agents, and suppression systems. Understand what is important to you and your company… reputation, product maturity, environmental profile, safety margins, known case studies, etc… Some suppression agent brands you'll want to consider: FM-200, Inergen, Argonite, Novec 1230. Also, because these halon alternatives are a more mature product set now, several application specific systems are available. For example, 'in-cabinet' systems for protection of a small closet or cabinet spaces; and one manufacturer provides FM-200 agent in a virtually 'drop-in' halon replacement type system.

2. Understand your company's overall FP strategies. Query other facilities, survey computer room locations or control room facilities. Talk to ris...


BROWSE BY TAG
Data center design and infrastructure,   Data center fire suppression,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center fire suppression
Drawbacks to hot/cold aisle containment
Hot-aisle/cold-aisle containment stokes fire-code issues
The Planet data center hosting company suffers major electrical fire
The data center EPO button: Is it even necessary?
Dry pre-action fire suppression systems
NFPA 75: Raised floor fire protection
Halon and FM-200, part two
Selecting a sprinkler system: Dependent on local building code regulations?
Gas fire suppression systems
Water versus gas-based data center fire suppression

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
limited combustible cable  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary


k management personnel. There may be diverging opinions within your own organization, so be prepared to support your conclusions.

3. Find trusted expertise. The science of special hazards fire protection is not simple. Know enough to know, you probably need help. However, even within the FP community, a thorough understanding of 'clean agents' can be difficult to find. Seek advice from colleagues within the data center community to find the right subject matter expert for you. Also, be involved with contractors and subs, know what you are specifying, and verify they are delivering it!

4. Understand local requirements. Many local authorities and municipalities will have their own interpretation of NFPA standards and other codes. A comprehensive understanding of these local requirements will save time and money in the long run.

5. Do a thorough risk assessment including TCO analysis of your facility. While some form of water based system (i.e. sprinklers) are likely required by code in your facility, do you really want them to go off, unless the assets are already a total loss? Understanding the levels of risk in your facility and the total cost to protect (or not to protect) against them is crucial.

6. Properly maintain the system throughout its useful life. All fire protection system manufacturers require authorized, factory trained service organizations to maintain the system for warranty coverage. It makes sense to do so. This is not an area where cost cutting should be considered. The only thing worse than not having any protection is thinking you have protection, but the system is inoperable due to poor maintenance!

7. Educate and train employees. The last thing you need at the time of an alarm is panic. Ask the installing contractor to provide on site training for all employees working in or near the facility being protected. Most will do so free of charge. Schedule training periodically to make sure your people understand and respect the protection systems installed.

About the author. Lance D. Harry is the Business Development Manager for Fenwal Protection Systems, a business unit of Kidde-Fenwal, Inc. Lance's primary responsibility is the establishment and enhancement of relationships within the Fenwal sales structure including distribution, technical influencers and users. Lance holds a master's degree from Boston University, and is a registered Professional Engineer, both in Mechanical Engineering. Lance has worked in a variety of technical, managerial, marketing and sales related positions within the fire protection community over the past 10 years including managing the product development and design activities in clean agent systems for Kidde-Fenwal, Inc., in Ashland, Mass. prior to joining the sales team with Fenwal. Click here to contact Lance.

Rate this Tip
To rate tips, you must be a member of SearchDataCenter.com.
Register now to start rating these tips. Log in if you are already a member.




DISCLAIMER: Our Tips Exchange is a forum for you to share technical advice and expertise with your peers and to learn from other enterprise IT professionals. TechTarget provides the infrastructure to facilitate this sharing of information. However, we cannot guarantee the accuracy or validity of the material submitted. You agree that your use of the Ask The Expert services and your reliance on any questions, answers, information or other materials received through this Web site is at your own risk.



White Papers - Data Center Networking

The Intel IT Technology Center - Power, Performance and Mobility Solutions

HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts