Home > Data Center News > Data center temperature range expanded: Who cares?
Data Center News:
EMAIL THIS

Data center temperature range expanded: Who cares?

By Mark Fontecchio, News Writer
27 Jan 2009 | SearchDataCenter.com

IT infrastructure news
Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google

CHICAGO – The American Society of Heating, Refrigerating and Air-conditioning Engineers has widened its recommended data center temperature and humidity ranges. But do the changes matter to users?

ASHRAE ASHRAE Technical Committee 9.9 (TC 9.9)members reported out on the expanded range last week during a session at the group's winter meeting in Chicago. The ASHRAE extended environmental envelope, as it's called, include the following:

  • Expansion of the recommended data center temperature range, which should be taken at the server inlets. They should now be 18 degrees Celsius to 27 degrees (64.4 degrees Fahrenheit to 80.6 degrees), expanded from 20 degrees to 25 degrees (68 degrees Fahrenheit to 77 degrees).
  • Data center humidity levels should now be measured by dew point and fall within 5.5 degrees Celsius to 15 degrees (41.9 degrees Fahrenheit to 59 degrees). The previous range was narrower and measured by relative humidity, which ASHRAE decided wasn't as accurate a metric as dew point. For details on the difference between the two, see "Data center humidity levels source of debate.")

"We went through a number of iterations," said Roger Schmidt, a distinguished IBM technologist and an ASHRAE member instrumental in the changes. "We looked at what vendors would be comfortable with." In the end, Schmidt said the group looked to expand the range "to provide greater flexibility in operations."

Temperature changes' impact on users
So does this change matter for users? Some organizations see ASHRAE as a leader in data center infrastructure and design. ASHRAE's expansion of the range allows for some data center efficiencies, such as being able to have the set points on the computer room air-conditioning (CRAC) units higher and not working as hard humidifying and dehumidifying the facility.

We went through a number of iterations.
Roger Schmidt,
ASHRAE member

"A higher supply temperature does improve energy efficiency," said Vali Sorell, an engineer at Syska Hennessy Group. "It allows for a higher supply air temperature so outside air can be available for more hours of the year." Sorell added that in data centers without economizers, it "also allows for a higher chilled water temperature."

But at least one user thinks the recommended range is still too narrow.

Christian Belady, the principal power and cooling architect at Microsoft, said end users shouldn't be "spending all their time and energy trying to hit that bull's eye," referring to the ASHRAE range.

"We need to convince organizations to run it outside of that range," he said.

According to Belady, Microsoft specifies in its requests for proposals (RFPs) that server vendors provide a much wider temperature and humidity range and warranty it. Indeed, among the four major server manufacturers – IBM, Hewlett-Packard, Sun Microsystems and Dell – recommended humidity levels are as low as 8% and as high as 90%, and recommended inlet server temperatures are as high as 84 degrees Fahrenheit.

"My plea to end users is to demand an even broader range, so we don't need all these controls," he said.

That's all well and good, but not everyone has as much pull as a company like Microsoft, which buys tens of thousands of servers every year. Robert Sullivan, a senior consultant at the Uptime Institute, said server vendors often notify smaller companies that warranties are null if the servers run outside ASHRAE's recommended data center temperature and humidity ranges.

Belady agreed and noted later that this was part of his point. Microsoft gets warranties for the much broader temperature and humidity ranges, so why does someone like Belady even care about ASHRAE's recommended ranges? It's a question he said his own boss has asked him.

"Because to me there's a greater good," he said. "At the end of the day, it doesn't really matter to me. But we should be running more efficiently as an industry, and not just as a corporation."

Let us know what you think about the story; email Mark Fontecchio, News Writer. You can also check out our Data Center Facilities Pro blog.



Tags: Data center power consumption and savingsData center coolingData center room design and locationVIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google



RELATED CONTENT
Data center power consumption and savings
APC adds monitoring, efficiency features to UPS line
IT wish list: Better ways to analyze data center environmental metrics
Data center colo scores energy rebates for UPS and more
Buyout could boost Uptime Institute
End users still cool on Iceland as a data center site
Reporter's notebook on AFCOM Data Center World: Day two
Notes from AFCOM Data Center World: Day one
U.S. versus global data center trends: IT priorities vary
Hot-aisle/cold-aisle containment takes hold
SPECpower benchmark has flaws, says analyst

Data center cooling
IT wish list: Better ways to analyze data center environmental metrics
End users still cool on Iceland as a data center site
Air-side economizers reduce energy use at NetApp data center
Sizing computer room air conditioners for data center energy efficiency
Should you comply with Article 645 of the National Electrical Code?
How to identify and remediate data center hot spots
Data center humidity levels source of debate
Air-side and water-side economizers in the data center
Amazon data center facility engineer touts radical cooling tactics
Colo taps cold weather, river for green data center
Data center cooling Research

Data center room design and location
Air-side economizers reduce energy use at NetApp data center
Data center location selection: Incentives can tip scales
Notes from AFCOM Data Center World: Day one
Microsoft cuts ribbon on mega data center
Hot-aisle/cold-aisle containment takes hold
How to identify and remediate data center hot spots
Colo taps cold weather, river for green data center
Preventing particle and gas contamination in the data center
Cleaning under the raised-floor plenum: Data center maintenance basics
AMD augments six-core Opteron chip line: News in brief
Data center room design and location Research

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
CADE (Corporate Average Data center Efficiency)  (SearchDataCenter.com)
economizer  (SearchDataCenter.com)
Energy Star  (SearchDataCenter.com)
fuel cell  (SearchDataCenter.com)
intelligent power management (IPM)  (SearchDataCenter.com)
LEED (Leadership in Energy and Environmental Design)  (SearchDataCenter.com)
Modular Datacenter  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Efficient Management for Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts