Monitoring data center contamination a key concern

By Mark Fontecchio, News Writer
26 Jan 2009 | SearchDataCenter.com

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   

CHICAGO – Has the time come for data centers to start monitoring their data center dust and pollution? According to experts at a recent industry conference, the answer is yes.

For more on data center design and infrastructure:
ASHRAE 2009 conference

Data center air-conditioning fans blow savings your way

Joe Prisco, a senior systems and technology group engineer at IBM, spoke Sunday, Jan. 26, at the ASHRAE Winter Conference in Chicago. He and two IBM colleagues – Prabjit Singh and Roger Schmidt -- wrote a paper on data center particulate and gaseous contamination.

Any kind of data center contamination -- and there are several types -- can cause problems, said Prisco. He started with data center dust, saying it could be separated into "chemically inert dust" and "corrosive dust."

Chemically inert dust is similar to household dust, and when it starts clogging server intake valves and other small openings, it can affect thermal efficiency, cooling efficiency, and the airflow through heat sinks in electronic components. It can also lead to overheating of power connectors for tape and optical media drives, he said.

Showing a picture of the dust, Prisco pointed out that there was "contamination evidence on covers and intakes."

"It's like a dust bunny is forming," he said.

Corrosive data center dust contains ionic chemical compounds like sulfur and chlorine salts that, when wet, get corrosive. When bridges form between two conductive patterns, Prisco said that short-circuiting can result.

After the session, Prisco added that a lot of the data center contamination comes from IT equipment being delivered in smaller and smaller footprints.

"The openings get smaller, and so the opportunities for bridging are there," he said. "Dust can pile up more easily."

Gaseous contamination and corrosion can come from outside gases -- sulfur dioxide, hydrogen sulfide and nitrogen dioxide -- that make their way into data centers. When two or more of these gases contact one another, he said "you can have a synergy of gases that compound the effect."

To monitor gases, Prisco and the other researchers used "copper coupons" – which look like blank server nameplates. Over time the copper builds a film of corrosion on it, which can be measured.

Data center contamination and air-side economizers
Overall, Prisco recommended monitoring data center dust and gaseous contamination. But in particular he suggested that those using or considering air-side economizers should monitor carefully.

"If you're looking into air-side economizers, which I know a lot of people are doing, it would be a good idea to start doing real-time monitoring of dust," he said, later adding that "I'm not saying don't use them, but you need to be careful about monitoring the dust and gaseous contaminants."

William Tschudi, a member of the Lawrence Berkeley National Laboratory (LBNL), took issue with that., however Tschudi was instrumental in a 2007 LBNL study that found that cooling data centers with outside air could save money and wouldn't ruin IT equipment. LBNL found that compounds called hygroscopic salts, when combined with high humidity, can cause equipment to shut down. But Tschudi said filtration systems in most data centers do just fine in keeping contaminants out.

According to the report, "IT equipment reliability degradation due to outdoor contamination appears to be a poor justification for not using economizers in data centers."

Yesterday Tschudi questioned the timeline of data center dust and gaseous contamination. In particular, he was interested in whether corrosion could be strong enough to shorten the normal server refresh cycle.

Prisco said that it all depends on the environment, but that he's seen situations in which computer components fail at a fast rate. He then stressed that he thinks monitoring of data center contamination should be done with all data centers, not just those with air-side economizers. He also said monitoring for contamination could prevent corrosion, whereas once the contamination is in there, it can get difficult to clean it without augmenting the problem.

Let us know what you think about the story; email Mark Fontecchio, News Writer. You can also check out our Data Center Facilities Pro blog.



Tags: Data center design and constructionData center coolingVIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Data center design and construction
Hewlett-Packard pushes smaller containerized data center
Facebook bets on coal for new Oregon data center
Oracle energy czar brings data center containment into vogue
Hot-aisle/cold-aisle containment slideshow
eBay's hot/cold-aisle containment in the data center
Yahoo's data center cold aisle containment
eBay uses plastic sheeting for data center hot cold aisle containment
Liebert's data center cold aisle containment product
Hot aisle / cold aisle containment in pictures
APC's data center hot-aisle containment

Data center cooling
Green Grid hones PUE data center efficiency metric
Facebook bets on coal for new Oregon data center
Oracle energy czar brings data center containment into vogue
Hot-aisle/cold-aisle containment slideshow
eBay's hot/cold-aisle containment in the data center
Yahoo's data center cold aisle containment
eBay uses plastic sheeting for data center hot cold aisle containment
Hot aisle / cold aisle containment in pictures
APC's data center hot-aisle containment
Liebert's data center cold aisle containment product
Data center cooling Research

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)
grumble line  (SearchDataCenter.com)
Modular Datacenter  (SearchDataCenter.com)
TIA-942  (SearchDataCenter.com)
tin whiskers  (SearchDataCenter.com)
unified computing system (UCS)  (SearchDataCenter.com)
Uptime data center tier standards  (SearchDataCenter.com)
water cooling  (SearchDataCenter.com)
zinc whiskers  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Efficient Management for Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2010, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts