ASHRAE to expand recommended data center humidity, temp ranges

By Mark Fontecchio, News Writer
19 Nov 2007 | SearchDataCenter.com

IT infrastructure news
Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google

The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) may expand its recommended ranges for data center humidity and temperature to help users save energy without compromising IT equipment safety.

For more on data center humidity:
ASHRAE to expand recommended server temp and humidity range

Data center managers try shutting off humidity controls

Data center humidity levels source of debate

Currently the group's recommended range for data centers is 20 degrees Celsius to 25 degrees Celsius (68 degrees Fahrenheit to 77 degrees Fahrenheit) for temperature and 40% to 55% relative humidity.

"I think it's really important from an energy standpoint if we can widen that range," said Roger Schmidt, a distinguished IBM technologist and chairman of ASHRAE Technical Committee 9.9 (TC 9.9), which focuses on computer rooms, in a recent podcast. "Obviously it depends on what the IT manufacturers will come back and say what they feel is acceptable from a reliability standpoint."

At the end of the day, I don't want to be arguing with IBM about my room being 78 degrees.
Brad Kowal,
associate data center director, Shands HealthCare

In most modern data centers, air-cooling units, such as computer room air-conditioners, or CRACs, in a raised-floor environment, overhead coolers, or units nestled in a row of server racks, display a relative humidity reading that data center managers can adjust. Preventing data center humidity from climbing too high or dipping too low prevents condensation from forming on your equipment and the possibility of electrostatic discharge, both of which can be harmful to computer equipment.

Pushing the envelope
ASHRAE does have a wider "allowable" range; its "allowable" relative humidity, for example, is 20% to 80%. This range is more in line with manufacturers' recommendations for servers. Dell Inc., for example, recommends 20% to 80%; HP recommends 15% to 80%; IBM, 8% to 80%; and Sun, 10% to 90%, according to various corporate Web sites. Maximum wet-bulb temperature recommendations can also get as high as 84 degrees Fahrenheit.

"The end users we've spoken to, they're OK with expanding the range a little bit," said Herb Villa, a TC 9.9 member and a field technical manager at Springfield, Ohio-based Rittal Corp. . "They can see the tangible benefits for system and facility performance and energy savings."

Where does the savings come from? By allowing a wider humidity range, a data center's air conditioners can focus on just blowing cool air. Trying to control humidity manually can be counterproductive, causing cooling units to fight one another when humidity levels differ throughout a room. If one unit, for example, is humidifying a room as another dehumidifies, the units cancel one another out and use extra electricity in the process.

Earlier this year, Shands HealthCare in Gainesville, Fla. shut off the humidity controls in its 3,500-square-foot data center. It's not unprecedented; Intel Corp. started doing it three years ago and now doesn't control humidity in about 50,000 square feet of data center space. Brad Kowal, Shands' associate data center director, said he would like to stay in the 30%-to-70% relative humidity range. As the more dry winter months of December, January and February approach, he'll keep an eye on it.

Kowal said he's glad to hear that ASHRAE will expand the recommended range, which he thinks is too tight right now.

"Yes, I want the ASHRAE data to keep pushing the logical envelope," he said. "It was not logical to me to have data center boundaries between 40[%]and 55[%] humidity in a 72-degree room when the manufacturers have it much wider."

"Do I want my data center to be 85 degrees? Probably not," Kowal continued. "But I think we can get energy savings and save the company some costs by taking a 72-degree room to 78. At the end of the day, I don't want to be arguing with IBM about my room being 78 degrees."

Villa agreed, adding that the ASHRAE move would be less about changing the range and more about changing mindsets concerning data center temperature and humidity.

"They're making sure the message is consistent," Villa said. "They're moving that box to make it more consistent with equipment manufacturers. They're not changing anything, perhaps, besides what people think."

Let us know what you think about the story; email Mark Fontecchio, News Writer. You can also check out our Server Specs blog.



Tags: Data center coolingData center power consumption and savingsVIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google


RELATED CONTENT
Data center cooling
Hot-aisle vs. cold-aisle containment: Liebert and APC face off
Core4 sells more efficient -- and costly -- CRACs
Grow a green business: Cut costs and improve energy efficiency with green IT
At colo data center, air mixing happens up high
Intel offers data center management software: News in brief
Data Center Facilities IT Handbook
IBM tightens ties with Cisco rival Brocade: News in brief
Lowering data center cooling costs with airflow modeling and perforated raised-floor tiles
Closing the green gap: Expanding data centers with environmental benefits
Green Grid tool assesses free cooling potential
Data center cooling Research

Data center power consumption and savings
The TPC Energy Specification: Energy consumption vs. performance and costs
Measuring data center energy consumption in watts per logical image
Data center managers plan for power density jumps
Backup power in a shipping container: Active Power's PowerHouse
Schneider: IT and energy management control systems bring efficiency
Grow a green business: Cut costs and improve energy efficiency with green IT
Lowering data center cooling costs with airflow modeling and perforated raised-floor tiles
Closing the green gap: Expanding data centers with environmental benefits
Preventing a data center power outage
AFCOM's Data Center World spring 2009 conference coverage

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
ambient temperature  (SearchDataCenter.com)
ASHRAE  (SearchDataCenter.com)
Calibrated Vectored Cooling  (SearchDataCenter.com)
compaction  (SearchDataCenter.com)
computer room air conditioning unit  (SearchDataCenter.com)
data center chiller  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)
hot/cold aisle  (SearchDataCenter.com)
HVAC  (SearchDataCenter.com)
water cooling  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Efficient Management for Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts