New low-sulfur diesel may hinder data center generators

By Mark Fontecchio, News Writer
06 Aug 2007 | SearchDataCenter.com

IT infrastructure news
Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google

A federal rule limiting the use of sulfur in diesel fuel is taking effect, and it could limit the performance of the generators that back up your data center.

For more on data center backup:
Weighing centralized versus modular UPS in the data center

UPS maintenance outage

In 2004, the Environmental Protection Agency (EPA) passed the Clean Air Nonroad Diesel Rule. But this June, its requirements took effect; now the amount of sulfur allowed in the diesel fuel for offroad engines -- such as agricultural equipment, some construction vehicles and backup generators -- has decreased. Previously the amount was unregulated and typically more than 3,000 parts per million (ppm). Now it must be less than 500 ppm.
I don't think the impact is going to be so huge that there will be thousands of generators across America that will no longer be sufficient.
Eric Gallant,
senior account manager, Lee Technologies

By June 2010, that cap drops again, to less than 15 ppm. The EPA wants to reduce the amount of sulfur in diesel fuel because the particles from high-sulfur fuel can cause pollution and acid rain.

Using ultralow-sulfur diesel fuel could affect how your generators run, said Eric Gallant, a senior account manager at Lee Technologies, a data center consulting and services company in Fairfax, Va.

Generator inefficiencies
A central issue is that ultralow-sulfur diesel fuel has less energy content, so generators may be unable to respond to sudden changes in load, said Gallant. In rare cases, a generator that is accustomed to operating at maximum capacity may have a lower maximum capacity, which could limit the ability of a generator to back up a data center.

Further, the lower energy content causes the fuel to be slightly less efficient, which means you'll need more diesel fuel to get the same amount of energy from it. Add to that the likelihood that fuel suppliers will charge more for ultralow-sulfur fuel because they have to remove the sulfur from it, and it could equal even higher fuel costs for data centers.

Perhaps more importantly, Gallant said the process by which fuel suppliers remove the sulfur also removes some of the lubricating properties of the fuel.

"There's a higher possibility of some kind of electrical discharge accident, causing a fire and hurting somebody," he said. "This comes down to a safety issue."

Gallant predicted that despite the drawbacks, most diesel fuel suppliers will not wait until 2010 to bring the sulfur level below 15 ppm. They'll do it now so they don't have to deal with the incremental change today, and then again in 2010.

But not everyone is concerned about the change. At Equinix Inc., a major data center hosting company in Foster City, Calif., Jay Park, director of systems engineering, doesn't think the change will significantly affect performance. Some fuel additives can help restore the lubricating properties of the fuel, although Park said that Equinix might incur minor additional maintenance costs for the fuel system because of the lower lubrication of the engine.

Concerning reduced energy capacity, Park said it is minor -- on the order of 1% to 2% at most. "The diesel engines usually have this much excess capacity above the generator set-rated capacity," he said. "Additionally, the maximum design operating loads on our systems are well below levels affected by this fuel change."

Gallant agreed. "I don't think the impact is going to be so huge that there will be thousands of generators across America that will no longer be sufficient," he said. "You're just not going to get as much out of diesel fuel per gallon, and you won't get as much out of your diesel engine."

Once data center operators switch to low-sulfur fuel, Gallant recommended that they consider the following issues:

  • Budget. Review your budget for the extra cost of the new fuel, which will get less mileage per gallon, so to speak, as well as have a higher cost per gallon.
  • Load transmission. Consider how electrical loads are brought to the generator. If loads can be put on more gradually, engines will respond better than by doing a step load, for example (where sources of uninterruptible power supply (UPS) are suddenly transferred to a generator.
  • Testing. During your first year of using the new fuel, test it more regularly. All diesel fuel has some microbial growth in it. The change in fuel might cause some sediment and contamination to break loose and float in the tanks, affecting fuel performance.
  • Guidance. Plenty of data centers out there aren't even aware of the new rule. Your fuel provider can be a good source of guidance on this front.
    "People who own generators need to ask providers, ' What are you doing to handle this?' " Gallant said. But even providers, he noted, "aren't aware of all the changes."

Let us know what you think about the story; e-mail Mark Fontecchio, News Writer.

Tags: Data center disaster recovery planningVIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google



RELATED CONTENT
Data center disaster recovery planning
Data center pros must prepare for increased space weather
Are you wasting disaster recovery budget to avoid employee inconvenience?
Four ways to extend data center UPS battery life
Why SunGard uses flywheel UPSes in its data centers
Lower disaster recovery costs with open source replication tools
Apple updates Xserve, Symantec ships DR monitoring software: News in brief
Data center disaster recovery planning
Google opts for battery backup over UPS: News in brief
Avoiding disaster recovery pitfalls in VMware and Linux: Rejecting default settings
Make IT change management part of your disaster recovery plan
Data center disaster recovery planning Research

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
Business Continuity and Disaster Recovery (BCDR)  (SearchStorage.com)
high availability  (SearchDataCenter.com)
RAIN  (SearchDataCenter.com)
uninterruptible power supply  (SearchDataCenter.com)
Uptime Institute, Inc.  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Efficient Management for Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts