Home > Data Center News > APC 'capture index' measures airflow in the data center
Data Center News:
EMAIL THIS

APC 'capture index' measures airflow in the data center

By Mark Fontecchio, News Writer
27 Feb 2007 | SearchDataCenter.com

IT infrastructure news
Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google

Jim VanGilder, a principal engineer with American Power Conversion Corp.'s (APC) data center cooling simulation group, recently gave a presentation at the American Society of Heating, Refrigerating and Air-Conditioning Engineers' (ASHRAE) annual conference in Dallas regarding a new metric to measure airflow efficiency. We caught up with VanGilder to ask him what it's all about.

Can you explain the capture index?

Jim VanGilder: It's a metric expressed as a percentage from zero to 100 for each rack in a data center. The value of 100% implies that all the airflow, either entering or leaving the rack, is following a desirable path.

More on data center airflow
Improved airflow cools off overheated data center

Should I use grate-type tiles in my raised flooring?

Raised floor bests overhead cooling, IBM finds

What do you mean by 'desirable path'?'

VanGilder: It depends on the application, but if you think of a common raised-floor design, you would like the airflow to come from the perforated tiles and then go into the racks. You wouldn't want air to the racks to come from the room. As for leaving the rack, the desirable path would be when you have local return vents or local coolers that capture the air coming from the racks.

Why are there two versions of the capture index, the hot aisle and cold aisle?

VanGilder: The capture index may be used to assess either delivery of cooling to the rack -- that's the cold-aisle version. Or it can be used to measure the scavenging or capturing of hot air from the rack, and that's the hot-aisle version.

The hot-aisle capture index is generally used if the design includes local coolers, like APC's InRow cooling products, or some other type of local return vent. This is because if you're capturing the hot air locally, you can design your data center around a room-neutral strategy, the goal of which is to prevent any hot air exhaust (from equipment) from escaping into the data center room environment. The benefit is the vast majority of air in the data center is maintained at some desirable room temperature. Since all the IT equipment is going to be provided with consistent room temperature air, regardless of where it comes from, you don't have to worry about the delivery of the cooling air to the rack. All IT equipment, whether at the bottom or the top of the rack, will see uniformly conditioned air.

In a typical raised-floor facility, however, the hot exhaust air isn't captured locally, but typically travels all the way back to CRAC units, which are located across the room. So you have to focus on the delivery of the cold air.

So you use the hot-aisle capture index as the preferred method if you can, if you have local cooling methods. Use the cold-aisle capture index if you don't.

There are already a lot of metrics out there for data centers. What differentiates this one, and why is it important?

VanGilder: There are other metrics, and each of them serves a valuable function. The main differentiator is that this is the only metric based on airflow patterns. Others are based on temperature.

The temperatures don't tell the whole story when it comes to cooling performance. Imagine a group of racks in a typical raised-floor environment, and these racks are clustered around a single cold aisle with perforated tiles. Now imagine a really horrible airflow pattern where some racks are drawing exclusively from the ends of the aisle or from recirculated air from the other side of the racks, and not the perforated tiles. If the surrounding room temperature is low enough, and there's enough air movement around, the rack inlet temperatures might be OK. But intuitively, this is not the kind of data center we want to design because as the surrounding room temperature changes, the rack inlet temperatures will change.

However, if we had computed the capture indices in the beginning, we would have known that the rack inlet temperatures were OK, but the capture indices were not. That could compromise cooling performance down the road.

Will having a good capture index lead to lower cooling costs?

VanGilder: I think that's a good point, but I'm not sure it would hold in all cases. It's application specific. I think it's a likely scenario because the index is a measure of whether the air is going where you want it to go.

How can data centers measure their own capture index?

VanGilder: The capture index is typically computed in the design process as part of a CFD [computational fluid dynamics] analysis or using some other dedicated tool. The capture index can help you find an optimum range of equipment and discover where potential airflow problems may exist through failure scenario investigations.

Physically measuring the capture index in a working data center is difficult. You could do it with a smoke test, but it's something that is best predicted numerically. But those who want to see what the problems are, if they were to do a CFD analysis or use APC's InfraStruXure Designer, it would provide some good clues as to what the underlying problems are. It would hasten the way toward a solution.

How did the capture index come about?

Van Gilder: My team is responsible for developing cooling calculators for InfraStruXure Designer software. The software is used by APC engineers and channel partners to provide data center design solutions for our clients. We also have a group called the APC Science Center, which is responsible for vast numbers of white papers on various topics, so some of the work by the APC Science Center fed into the work my team has done.

Let us know what you think about the story; e-mail: Mark Fontecchio, News Writer, and check out the SearchDataCenter.com Blog.

Tags: Data center coolingData center room design and locationVIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us    Add to Google



RELATED CONTENT
Data center cooling
IT wish list: Better ways to analyze data center environmental metrics
End users still cool on Iceland as a data center site
Air-side economizers reduce energy use at NetApp data center
Sizing computer room air conditioners for data center energy efficiency
Should you comply with Article 645 of the National Electrical Code?
How to identify and remediate data center hot spots
Data center humidity levels source of debate
Air-side and water-side economizers in the data center
Amazon data center facility engineer touts radical cooling tactics
Colo taps cold weather, river for green data center
Data center cooling Research

Data center room design and location
Air-side economizers reduce energy use at NetApp data center
Data center location selection: Incentives can tip scales
Notes from AFCOM Data Center World: Day one
Microsoft cuts ribbon on mega data center
Hot-aisle/cold-aisle containment takes hold
How to identify and remediate data center hot spots
Colo taps cold weather, river for green data center
Preventing particle and gas contamination in the data center
Cleaning under the raised-floor plenum: Data center maintenance basics
AMD augments six-core Opteron chip line: News in brief
Data center room design and location Research

Data center design and infrastructure
Hewlett-Packard demonstrates its Performance Optimized Data center (POD)
CRG West preps data centers for cloud computing customers
Six tips for designing a cost-effective data center
Pros and cons of international data center locations
Uptime conference goers mull data center efficiency
Cooling data centers with outside air gets the go-ahead
More perforated tiles equal better data center cooling
Sun servers study Sun's energy at Princeton lab
Raised floor bests overhead cooling, IBM finds
Improved airflow cools off overheated data center

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
ambient temperature  (SearchDataCenter.com)
ASHRAE  (SearchDataCenter.com)
Calibrated Vectored Cooling  (SearchDataCenter.com)
compaction  (SearchDataCenter.com)
computer room air conditioning unit  (SearchDataCenter.com)
data center chiller  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)
hot/cold aisle  (SearchDataCenter.com)
HVAC  (SearchDataCenter.com)
water cooling  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Efficient Management for Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts