Home > Ask the Data Center Experts > Physical environment/power and cooling Questions & Answers > Data center cooling and humidity control: CRAC or AHU?
Ask The Data Center Expert: Questions & Answers
EMAIL THIS

Data center cooling and humidity control: CRAC or AHU?

Robert McFarlane EXPERT RESPONSE FROM: Robert McFarlane

Pose a Question
Other Data Center Categories
Meet all Data Center Experts
Become an Expert for this site


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


>
QUESTION POSED ON: 07 October 2007
We are in the midst of finalizing our data center design and keep going back and forth on the following:
  • CRAC units or rooftop AHU?
  • Raised floor or attached cabinets to the slab?
  • Hot aisle/cold aisle with forced enclosures on hot aisle or not?

This will be an approximately 7,200-sq. ft data center. There will be approximately 500-700 servers, a mainframe, a Xerox printer, and NOC that staffs the data center 24x7. Any advice?



BROWSE BY TAG
Physical environment/power and cooling,   Data center design and infrastructure,   Data center room design and location,   Data center cooling,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


RELATED CONTENT
Physical environment/power and cooling
Are energy-efficient KVMs next?
Powering modems with SMPS-based power supplies
Weighing centralized versus modular UPS in the data center
Overheating servers
UPS maintenance outage
More on power supplies
Dual power question
CRAC units with existing HVAC
Ideal data center components
The most important trend in data center business

Data center room design and location
Hot-aisle vs. cold-aisle containment: Liebert and APC face off
Core4 sells more efficient -- and costly -- CRACs
Hewlett-Packard demonstrates its Performance Optimized Data center (POD)
Schneider: IT and energy management control systems bring efficiency
Sun Microsystems releases new version of OpenSolaris
Where and how to build your next data center in a down economy
HP updates mission-critical services: News in brief
Ascent builds customizable data center hosting facility: News in brief
Data center air recycling saves cash-strapped greenhouse
At colo data center, air mixing happens up high
Data center room design and location Research

Data center cooling
Hot-aisle vs. cold-aisle containment: Liebert and APC face off
Core4 sells more efficient -- and costly -- CRACs
Grow a green business: Cut costs and improve energy efficiency with green IT
At colo data center, air mixing happens up high
Intel offers data center management software: News in brief
Data Center Facilities IT Handbook
IBM tightens ties with Cisco rival Brocade: News in brief
Lowering data center cooling costs with airflow modeling and perforated raised-floor tiles
Closing the green gap: Expanding data centers with environmental benefits
Green Grid tool assesses free cooling potential
Data center cooling Research

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
data center  (SearchDataCenter.com)
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)
grumble line  (SearchDataCenter.com)
Modular Datacenter  (SearchDataCenter.com)
TIA-942  (SearchDataCenter.com)
tin whiskers  (SearchDataCenter.com)
Uptime data center tier standards  (SearchDataCenter.com)
water cooling  (SearchDataCenter.com)
zinc whiskers  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary


The size of your data center and the number of servers justifies an uncompromising design. Computer Room Air Conditioners (CRACs) are precisely what the name implies: air conditioners designed specifically for the needs and demands of the computer room. I'm assuming from the wording of your question that the roof-mounted Air Handling Units (AHUs) that you are also considering are conventional units designed for the standard office environment, and probably run off the building central system. A data center should be as independent as possible.

It is unlikely that standard rooftop AHUs will maintain the close tolerance temperature and humidity control you should have in a high-availability data center environment, which it appears you intend to have if you are staffing the NOC 24x7. (Incidentally, the NOC should be provided with a normal office environment to make it more comfortable and controllable for the occupants.) Standard AHUs are normally designed to handle more latent heat (evaporation of moisture from human activity), whereas CRACs are designed to humidify while also handling mostly sensible heat (the dry heat you feel or sense coming off of computer hardware).

You don't identify where in the country you are located, but if you are in the North, roof-mounted AHUs can present some operational and maintenance problems in deep winter, and if you're in the South, they may not provide the level of humidity control you need. With today's concerns about energy efficiency, you will probably also find CRACs to be more economical in the long run, particularly if you are in a part of the country where you can take advantage of winter temperatures to utilize "free cooling."

The raised floor question is one that is widely debated these days. I still prefer a raised floor in most situations, particularly if I have enough building height to utilize the floor for air delivery. (That means 18-inches minimum, and preferably 24-30 inches. It also means controlling obstructions under the floor, including piping, power and cable.) With roof-mounted AHUs, you're not going to deliver the air to the floor, so it becomes a matter of personal preference and budget. I still like to have power and permanent cable infrastructure under the floor if I can, but others have different opinions.

If you can't make a raised floor high enough to use it for efficient air delivery, then, whether you use roof-mounted AHUs or CRACs, you will be delivering air from overhead. This can certainly be done, and can be done well, but it requires more design than simply blowing cold air into the room. Warm air rises, so dumping cold air in from above in the closely-coupled "Hot Aisle/Cold Aisle" design of a data center essentially contradicts the laws of physics since the warm air will rise and mix with the cold. Either solution will require well-designed ducting to cool and operate efficiently. Therefore, this is probably easier to do, and certainly less space consuming, with roof-mounted AHUs for which the return is already at the ceiling. On "Top Blow" CRACs the return air intake is at the lower front or back of the unit, which presents greater duct design problems. In my opinion, however, unless other factors preclude it, I would opt for CRACs in an important facility every time.

If I'm interpreting your question correctly, you are asking if you should use enclosures with fans mounted on the rear doors, blowing into the hot aisles. I consider most of the "fan boosted" solutions to be means of addressing problems caused by a poor basic cooling design. I say "most" because there are cabinets that are truly engineered to support higher density loads than can be achieved with high-flow cabinet doors alone, even in a well designed facility. But these cabinets generally duct the hot air to an isolated return path – usually a plenum ceiling – so they are solving more than just an air flow problem; they are also preventing re-circulation of hot air, which in itself makes a big difference. Remember, however, that fans will try to pull air out of the floor or cold aisle in the quantity they were designed for, and this may air-starve other equipment farther down the row. (Variable speed fan control helps, but if heat load is high the fans will still try to pull maximum air.) A data center is a complete "system," and you can't just insert a "solution" into the middle of it without affecting things elsewhere. There is simply no "magic bullet" for the problem of high-density cooling.




Search and Browse the Expert Answer Center
Search and browse more than 25,000 question and answer pairs from more than 250 TechTarget industry experts.
Browse our Expert Advice



Building Green Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts