Overheating servers

Robert McFarlane EXPERT RESPONSE FROM: Robert McFarlane

Pose a Question
Other Data Center Categories
Meet all Data Center Experts
Become an Expert for this site


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


>
QUESTION POSED ON: 22 April 2006
We have an Intel base thin server, 1U and 2U. We are using a Dell rack, 42U. We are stacking almost all of this rack with these servers. It is really overheating. Is there any recommendation for the number of servers that should be in this rack? Should we consider a space between each server? Maybe 1U size? I read one of your articles about cooling and, as you said with cooling coming from bottom to top, the servers on the top are really overheated. What is your recommendation and/or suggestions?

>
You have the classic problem facing the majority of your colleagues today. Most data centers were never designed for the kinds of heat densities that full cabinets of small form factor servers (1U and 2U) create. There are three potential reasons for the overheating:

  1. You aren't getting enough of your available cooling to these cabinets.
  2. You don't have enough cooling to support the amount of heat being generated in the room.
  3. Both of the above.

There are only two ways to address the problem:

A) Modify or properly add to your air conditioning and/or air delivery.

B) If you do have enough total cooling, space out your equipment to reduce the number of servers and, consequently, the heat load, in each cabinet.

The first thing is to get the most out of the air conditioning you already have. Read my article entitled "Block those holes!". If that doesn't help, either you don't have enough cooling capacity, or what you have is improperly designed and/or isn't getting the available air to the equipment. Make sure you're not simply blocking under-floor air with cables, and that your air conditioners have been properly serviced and are working properly.

Spacing out the servers does not mean putting 1U between boxes. It's unlikely this will help much, except in simply reducing the total load in each cabinet. Hot air rises, so the intake air will be warmer by the time it reaches the top of the cabinet than it was when it came out of the floor. And some of the hot air from the back "hot aisles" will inevitably go over the tops of the cabinets, re-entering the upper servers. As you've correctly observed, it's no wonder that the servers at the top of the cabinets tend to get the hottest. Therefore, as a general rule, load the cabinets from the bottom up, starting about four or five U's from the bottom with a blank panel. And block the remaining space with blank panels as well.

"Spacing" means leaving two or more lightly-loaded cabinets between the higher loaded ones. In legacy data centers, we usually suggest no more than fifteen to twenty 1U servers in a cabinet as a "rule of thumb", but this is totally dependent on the power demand of each server, and the air delivery available. I would suggest starting with the problem cabinets only half full and seeing if there's enough improvement. Also make sure that cables are not blocking the rear exhausts of the servers.

If this doesn't help enough, and you've taken all the steps to get the most out of the air conditioning you have, you may need more cooling capacity. There are a number of new solutions on the market, and more coming, but this is an expensive and potentially disruptive undertaking. Read my articles "Let's add an air conditioner" and "Cabinets, bloody cabinets!". In general, I would probably not recommend simply adding another CRAC Unit. Rarely can it be put where it will really solve the problem, and often it will actually create new ones. Look at localized overhead cooling, in-row cooling, or even self-cooled cabinets. These all require infrastructure of some kind but, if properly selected, designed and used, any of these will likely be more cost-effective and flexible than rolling in another big air conditioner and enduring the disruption of welding and soldering in your data center.

I would be remiss if I didn't also note that there are computerized analysis tools that, in the hands of an expert, can pinpoint problems and help in developing solutions before a lot of money is invested.


BROWSE BY TAG
Physical environment/power and cooling,   Data center design and infrastructure,   Data center room design and location,   Data center network cabling,   Data center cooling,   VIEW ALL TAGS

Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   



RELATED CONTENT
Physical environment/power and cooling
Are energy-efficient KVMs next?
Powering modems with SMPS-based power supplies
Data center cooling and humidity control: CRAC or AHU?
Weighing centralized versus modular UPS in the data center
UPS maintenance outage
More on power supplies
Dual power question
CRAC units with existing HVAC
Ideal data center components
The most important trend in data center business

Data center room design and location
Air-side economizers reduce energy use at NetApp data center
Data center location selection: Incentives can tip scales
Notes from AFCOM Data Center World: Day one
Microsoft cuts ribbon on mega data center
Hot-aisle/cold-aisle containment takes hold
How to identify and remediate data center hot spots
Colo taps cold weather, river for green data center
Preventing particle and gas contamination in the data center
Cleaning under the raised-floor plenum: Data center maintenance basics
AMD augments six-core Opteron chip line: News in brief
Data center room design and location Research

Data center network cabling
Data center cabling management: Mind over matter
Should you comply with Article 645 of the National Electrical Code?
IBM tightens ties with Cisco rival Brocade: News in brief
IBM/Brocade deal reeks of Cisco hostility
A data center relocates on New Year's Eve
Dell/Cisco partnership may simplify data center infrastructure
27 tips for good data center design
Bank refreshes outdated data center with PDUs, new CRAC units
PDU Cables showcases new offerings
Data center managers' holiday wish lists
Data center network cabling Research

RELATED GLOSSARY TERMS
Terms from Whatis.com − the technology online dictionary
data center  (SearchDataCenter.com)
Electric plugs for each country  (SearchDataCenter.com)
green data center  (SearchDataCenter.com)
grumble line  (SearchDataCenter.com)
Modular Datacenter  (SearchDataCenter.com)
TIA-942  (SearchDataCenter.com)
tin whiskers  (SearchDataCenter.com)
Uptime data center tier standards  (SearchDataCenter.com)
water cooling  (SearchDataCenter.com)
zinc whiskers  (SearchDataCenter.com)

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Search and Browse the Expert Answer Center
Search and browse more than 25,000 question and answer pairs from more than 250 TechTarget industry experts.
Browse our Expert Advice



Building Green Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides technology professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective purchase decisions and managing their organizations' technology projects - with its network of technology-specific websites, events and online magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Site Map




All Rights Reserved, Copyright 2005 - 2009, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts