Home > Ask the Data Center Experts > Cooling Questions & Answers > Fine tuning hot aisle/cold aisle rack arrangements
Ask The Data Center Expert: Questions & Answers
EMAIL THIS

Fine tuning hot aisle/cold aisle rack arrangements

Steve Madara EXPERT RESPONSE FROM: Steve Madara

Pose a Question
Other Data Center Categories
Meet all Data Center Experts
Become an Expert for this site


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


>
QUESTION POSED ON: 18 December 2005
After reading your article on "Cooling high-density racks", posed on 03 August 2005, it seems to me that a configuration requiring that "hot aisle/cold aisle" rack arrangements in relative positioning to the air units keep the data center floor from being truly redundant. That is to say, if one of the air units failed, the return air from the hot aisle would not be properly cooled for re-use.

>
EXPERT RESPONSE

Very good question and observation. As each data center layout is a little different, it is recommended with the Hot Aisle/Cold Aisle rack arrangement to put the CRAC air units at both ends of the hot aisle. There are two situations to consider:

a) If the maximum heat load is less than the cooling load of all the CRAC units at the end of the Hot Aisles, then alternate CRAC units will and can act as the redundant cooling unit. Obviously, the airflow for each row may not be consistent. As will be noted in b) below, the use of a common plenum can help eliminate mixing of hot and cold air.

b) If the maximum heat load equals the cooling load of all the CRAC units at the end of the Hot Aisles, then space and location for the redundant units needs to determined. In this case, it would be recommended to add the redundant unit next to a unit at the end of a row and center the two units on the middle of the Hot Aisle (assumes the units are all 100% front access). This will then suggest that you rotate for equal wear the two units paired together so that one is available as a redundant unit. This however presents a problem in that if a unit fails and is not paired with a redundant unit, then your room balance could be off. To improve on this configuration, you could duct back to the CRAC units from either the complete Hot Aisle or from the center of the Hot Aisle using a common plenum (such as the space above a drop ceiling), to prevent the mixing of hot air across a Cold Aisle. With some supplemental cooling systems, the modules can be oriented to provide redundancy. This eliminates airflow across rows of racks and the need to be concerned with redundant CRAC units.


Digg This!    StumbleUpon Toolbar StumbleUpon    Bookmark with Delicious Del.icio.us   


RELATED CONTENT
Cooling
McFarlane tackles liquid cooled racks
Cooling high-density racks
The total cost of cooling

RELATED RESOURCES
2020software.com, trial software downloads for accounting software, ERP software, CRM software and business software systems
Search Bitpipe.com for the latest white papers and business webcasts
Whatis.com, the online computer dictionary



Search and Browse the Expert Answer Center
Search and browse more than 25,000 question and answer pairs from more than 250 TechTarget industry experts.
Browse our Expert Advice



Building Green Data Centers
HomeNewsTopicsITKnowledge ExchangeTipsBlogsMultimediaWhite PapersEvents
About Us  |  Contact Us  |  For Advertisers  |  For Business Partners  |  Site Index  |  RSS
SEARCH 
TechTarget provides enterprise IT professionals with the information they need to perform their jobs - from developing strategy, to making cost-effective IT purchase decisions and managing their organizations' IT projects - with its network of technology-specific Web sites, events and magazines.

TechTarget Corporate Web Site  |  Media Kits  |  Reprints  |  Site Map




All Rights Reserved, Copyright 2005 - 2008, TechTarget | Read our Privacy Policy
  TechTarget - The IT Media ROI Experts